Maintenance Label Image Upload
The door is a certified fire door complete with manufacturer's label, plug, or marking indicating it is a certified fire door.
Pass
Fail
N/A
Image Upload
Comments
ART number Select 01: Lipping Repair 02: Over Recessed Hardware 03: Door Frame Joints 04: Door Gaps Incorrect to Specification 05: Closer Not Operating Correctly 06: Door Leaf Out of Alignment 07: Moisture Content Too High 08: Hinges Dropped or Damaged 10: Operational Maintenance 11: Damaged Perimeter Seals 12: Misaligned Matching Hardware 13: Hinge Fixings Are Loose 14: Damaged Glazing and Glass 16: Installation of Replacement or Refitting Architrave and Sealing to Structural Opening 17: Replacement Door-Leaf 18: Recommendation for Replacement Doorset 19: Fire Door Signage 20: Replacement Door Frame 21: Repair Door Frame 22: Smoke Control 23: Calling In Expertise 24: Ineffectual Fixings
Can this door be considered a notional or nominal fire door (N/A if certified).
Fire door rating:
The door is free from distortion & holes.
The frame is securely attached to the wall, is free from distortion, damage, or holes.
The frame-to-door gap is consistently 3mm (tolerance of +/- 1mm).
Measurement of gap (3x measurements required):
Hinge Side:
Latch Side:
Top:
Floor-to-door gap is consistently 10mm (3mm, tolerance of +/- 1mm, if smoke door).
Measurement of floor to door gap:
If hung as a pair, do they close in line together (N/A if not pair).
Correct Fire Door signage fitted.
Intumescent strip is attached to the door or frame.
Intumescent strip continuous and free from damage.
Door fitted with cold smoke seals (N/A if non smoke door).
Cold smoke seals continuous, free from damage or breakage, free from paint or varnish and well attached to the door or frame (N/A if non smoke door).
Fire Door Hinges, marked with an appropriate "BS or EN" Number or CE Mark/UKCA.
Minimum of 3 hinges per door and all screws present and correct size.
Hinges free from wear, metal fragments, or oil leakage.
All ironmongery and components are free from visible damage and of the same fire rating as the door set (consider handles, locks, D handles, Push Plates, drop down seals, etc.).
Door closer present, operating correctly, free from damage and not leaking.
Open door 75mm release door closes and latches.
If glazed, the glass is fire rated.
No cracks or damage to glazing.
If glazed below 1500mm, the glass is safety glass.
Does the door need replacing?
Yes
No
Door Only (Internal Frame)
Door Set (Structural Opening)